SIMULATION OF NARROWBAND POWER LINE CARRIER COMMUNICATION FOR SMART GRID APPLICATIONS
DOI:
https://doi.org/10.55766/sujst-2023-02-e02016Keywords:
Power line carrier communication (PLCC), Wave trap, Channel modelling, Line tuner, Underground medium-voltage cable, Attenuation, Power line channelAbstract
For developing a reliable Power Line Carrier Communication (PLCC) system, it is extremely important to know the characteristics of different subsystems in PLCC and power lines. The circuit used to superimpose carrier signal from the transmitter with high potential power lines is termed as line tuners. The design and simulation of a capacitive type line tuner meeting IEC 60481:1974 and IEEE Std C93.4-2012 are included in this article. The wave trap allows the power signal to pass through but blocks the high-frequency carrier signal to reach terminal equipment which works at 50/60 Hertz. Three types of wave traps are studied as part of this paper: single frequency, dual frequency, and wideband wave traps. Impedance characteristics obtained in simulation show effective rejection of carrier signal as desired. The distribution power transformers are an inevitable part of the power line network which offers high attenuation to carrier signal as being inductive it functions as low pass filter. To overcome this problem a bypass circuit which could be incorporated in future power transformers is proposed in this article. The Resistance, Inductance, and Capacitance (RLC) parameter of the power line cable used in the simulation model are derived based on the experimental values observed on an actual 11 kV underground cable and thus replicates actual field conditions. A complete PLCC system with all the above components is presented in this article and can be used as a testbed by designers to validate the MODEM for communication in different topologies by modifying the elements according to actual field conditions.
References
Bureau of Indian Standards [BIS]. (2011). Crosslinked Polyethylene Insulated Thermoplastics Sheathed Cables, Part 2: for Working Voltages from 3.3 kV up to and Including 33 kV. ETD 09: Power Cables Sectional Committee, New Delhi, IS 7098 (Part 2): 2011. 14p. Available from: www.bis.gov.in.
Bureau of Indian Standards [BIS]. (1995). Line traps for AC power systems specification. LITD 10: Power System Control and Associated Communications, New Delhi, IS 8792: 1995. 11p. Available from: www.bis.gov.in.
General Electric Company [GE]. (2016). Line Traps - air core, dry type up to 800 kV. GE Grid Solutions, Ontario, GRID-AIS-L3-LineTraps-0247-201510-EN. 8p. Available from: www.gegridsolutions.com.
General Electric Company [GE]. (2013). Relaying Communication Channels: Application guide. GE Power Management, Ontario, GET-8034. 442p. Available from: www.GEindustrial.com/pm.
International Electrotechnical Commission [IEC]. (1989). Line traps for a.c. power systems. TC 57 - Power systems management and associated information exchange, Geneva, IEC 60353: 1989. 79p. Available from: www.iec.ch.
International Electrotechnical Commission [IEC]. (2012). Power line communication systems for power utility applications - Part 1: Planning of analogue and digital power line carrier systems operating over EHV/HV/MV electricity grids. TC 57 - Power systems management and associated information exchange, Geneva, IEC 62488-1:2012. 262p. Available from: www.iec.ch.
International Electrotechnical Commission [IEC]. (2017). Surge arresters - Part 8: Metal-oxide surge arresters with external series gap (EGLA) for overhead transmission and distribution lines of a.c. systems above 1 kV. TC 37 - Surge arresters, Geneva, IEC 60099-8:2017. 138p. Available from: www.iec.ch.
Institute of Electrical and Electronics Engineers [IEEE]. (2005). IEEE Guide for Power-Line Carrier Applications. Power System Communications Committee, New York, IEEE Std 643-2004. 140p. Available from: www.ieee.org.
Institute of Electrical and Electronics Engineers [IEEE]. (2015). IEEE Standard for Low-Frequency (less than 500 kHz) Narrowband Power Line Communications for Smart
Grid Applications - Amendment 1. Power Line Communications Standards Committee, New York, IEEE Std 1901.2a-2015. 28p. Available from: www.ieee.org.
Institute of Electrical and Electronics Engineers [IEEE]. (2013). IEEE Standard for Low-Frequency (less than 500 kHz) Narrowband Power Line Communications for Smart Grid Applications. Power Line Communications Standards Committee, New York, IEEE Std 1901.2-2013. 269p. Available from: www.ieee.org.
Institute of Electrical and Electronics Engineers [IEEE]. (2020). IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits (>1 kV). Surge Protective Devices Committee, New York, IEEE Std C62.11-2020. 120p. Available from: www.ieee.org.
Institute of Electrical and Electronics Engineers [IEEE]. (2013). IEEE Standard for Power-Line Carrier Line-Tuning Equipment (30 kHz to 500 kHz) Associated with Power Transmission Lines. Power System Communications Committee, New York, IEEE Std C93.4-2012. 67p. Available from: www.ieee.org.
Institute of Electrical and Electronics Engineers [IEEE]. (2017). IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz). IEEE Power and Energy Society, New York, IEEE Std C93.3-2017. 46p. Available from: www.ieee.org.
López, G., Matanza, J., De La Vega, D., Castro, M., Arrinda, A., Moreno, J. I., and Sendin, A. (2019). The Role of Power Line Communications in the Smart Grid Revisited: Applications, Challenges, and Research Initiatives. IEEE Access, 7(1):117346-117368. https://doi.org/10.1109/ACCESS.2019.2928391
Melit M., Nekhoul B., Sekki, D., and Kerroum K. (2012). Modelling of the transmission of power line communication signal trough the power electric transformer. Annals of Telecommunications (Springer), 67(9-10):447-454. https://doi.org/10.1007/s12243-011-0277-4
Pulsar Technologies, Inc., (Canada). (2013). Power line carrier channel and application considerations for transmission line relaying. AMETEK Power Instruments, New York, C045–P0597. 49p. Available from: www.ametekpower.com.
Vacuumschmelze GmbH and Co, (Germany). (2015). Isolation transformer for narrowband PLC systems. VACUUMSCHMELZE ADVANCED MAGNETIC SOLUTIONS, Hanau, T60403-K5024-X044. 3p. Available from: www.vacuumschmelze.com.