THE COMBINED AIR-CONDITIONING SYSTEM BETWEEN THE VAPOR COMPRESSION AND THE EVAPORATIVE COOLING SYSTEM
Keywords:
Evaporative cooling system, Combined air-conditioning systemAbstract
Improvement of an air-conditioning system was investigated. A combined air-conditioning system consising of a vapor compression and the modified drip type cooler of direct evaporative cooling system was designed and buit. The testing room had a 12,500 Btu/h cooling load. The designed system increased the performance of the vapor compression cycle by reducing the temperature of the air environment near the condenser using the water evaporative cooling system. A wall of the testing room exposed to the sun radiation was cooled by the water coming out of the evaporative unit. The experimental results showed that the coefficient of performance (COP) and the energy efficiency ratio (EER) of the combined air-conditioning system were about 5 and 13.7, respectively. The COP and the EER of the new system were higher than those of a vapor compression system about 41% and 46%, respectively.